No there is a real concern there. Suppose you have a daisy chain that goes breaker - PV panel - load. Say you have 20A draw on the load - enough to trip a 15A breaker, but the PV is providing 10A. In that case you only have 10A at the breaker, but your wires will be significantly over-current.